Installation
CS2000 Wiring:
The CS2000 comes with an 8' - 4 conductor cable. Refer below for wire designations.
RED = 10-30 VDC
BLK = Common
WHT = Output
ORN = NPN / PNP Output Selector
Optoisolator
CS2000
RED
10-30V
LOAD
BLK
WHT
ORN
WHT
ORN
WHT
ORN
WHT
ORN
WHT
+5V
5V Logic
1K
1/4W
Supply
Voltage
12V = 1K 1/4W
24V = 2K 1/4W
12V = 1K 1/4W
24V = 2K 1/4W
Optoisolator
*5V Com. and 10-30V Com.
must be connected together
*Output Source Com. and Supply
Com. must be connected together
*Resistor values are to source approx.
10mA to the optoisolator
*Resistor values are to source approx.
10mA to the optoisolator
ORN
WHT
ORN
CS2000
CS2000
CS2000
CS2000
CS2000
Interfacing to Load - NPN Output:
Interfacing to 5V Logic - NPN Output:
Sourcing Other than Supply Voltage - PNP Output:
Interfacing to Optoisolator - PNP Output:Interfacing to Optoisolator - NPN Output:
Interfacing to Load - PNP Output:
LOAD
LOAD
RED
10-30V
RED
RED
10-30V
BLK
BLK
10-30V
BLK
RED
10-30V
BLK
RED
BLK
10-30V
Output
Source
Voltage
10-30V